Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T12BU00319
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2012 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
04/24/2012 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | Need to label pull stations to each hood such as 1 or 2 - or - A or B hood Shall mount fire extinguisher on wall (K-class) Shelving over 6 burner stoves can not be more than 11 inches out. Make up air shut down - Passed Air test - Passed Placement and distances for nozzles - passed Gas shut down - passed Pull station - passed Cutting link - passed |
|
04/12/2012 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | IVRS - RI canceled |