Inspection History: FIRE - ALARM FINAL

Permit Number - T12BU00303

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2012 FIRE - ALARM FINAL Approved Permit paid -Demolation done - All fire doors in elevator lobbies fixed
07/30/2012 FIRE - ALARM FINAL Partial Approval It is okay to start the demolition of the existing fire alarm wiring and equipment.
07/25/2012 FIRE - ALARM FINAL Correction Required Tested Stairwell pressures
North South
Floor 22 .17 .17
Floor 11 .17 .23
Floor 5 .31 .29
Floor 2 .51 .55
Floor 2 to high over 30 pounds to open doors IFC 10088.1.1.2 Door Swing
On all floors elevator lobbies have problems with doors closing and latching need to repair or replace doors so all can close and latch,
Need to test fire pump to FACP
Need to test new valves installed and repairs made to tamper and flows
07/25/2012 FIRE - ALARM FINAL Partial Approval Partial approval given all testing done final will be given when inspections for after hours is paid for.
07/02/2012 FIRE - ALARM FINAL Cancelled IVRS - RI canceled
06/25/2012 FIRE - ALARM FINAL Cancelled Not ready to test repairs call and cancelled
Still need to test smoke removel system for stairs
Still need to test fire pump to panel.
06/15/2012 FIRE - ALARM FINAL Correction Required Tested flow and tamper switches on floors 1 to 24 after adjustments were made all passed with the exception of floor 11 tamper is failing will need to replace switch, also inspectors test valve is very hard to open and close valve hard to seat need to repair or replace.
Tested tampers and flow switches on levels P-1 to P-3 again after adjustment were made some passed but the following needs to be repaired or replaced:
1. Tamper switch P-1 inside parking garage by stairwell 3 failed
2. Tamper switch P-1 inside stairwell 3 failed
3. Flow switch P-3 stairwell 3 failed
4. Tamper switch on the fire pump test header failed
5. Flow switch on the main line in the fire pump room keeps sticking repair or replace.
06/14/2012 FIRE - ALARM FINAL Correction Required Floor 25 - Top of stairs need to add a smoke - Passed
Floor 24 - Need to turn up sounders to quite - Passed
Duct detectors tested - passed but A/C unit #9 is missing parts and not a working A/C unit, A/C unit #8 shut down. Elevator recall - Passed
Floor 23 - Stair well 1 smoke detector added at top of stairs - Passed
Floor 22 - North hall need to add horn/strobe to quite, horn/strobe added- Passed
Tested smoke detector in the returned air plenum - Passed
Floor 21 - Tested smoke detector in the returned air plenum - Passed
Floor 20 - Box phones not working in stairwells - Passed
Phone boxes in stair 1 and 2 tested - Passed
Tested smoke detector in the returned air plenum - Passed
Floor 19 - Tested smoke detector in the returned air plenum - Passed
Floor 18 - Tested smoke detector in the returned air plenum - Passed
Floor 17 - Tested smoke detector in the returned air plenum - Passed
Floor 16 - West tenant space stairwell add smoke and horn/strobe (keep smoke 3 feet away from all exhaust and intake vents) - Passed
Tested smoke detector in the returned air plenum - Passed
Floor 15 - West tenant space stairwell add smoke and horn/strobe (keep smoke 3 feet away from all exhaust and intake vents) - Passed
Tested smoke detector in the returned air plenum - Passed
Floor 14 - West tenant space stairwell add smoke and horn/strobe (keep smoke 3 feet away from all exhaust and intake vents) - Passed
Tested smoke detector in the returned air plenum - Passed
Floor 12 - Tested smoke detector in the returned air plenum - Passed
Floor 11 Elevator room needs horn/strobe - Added horn/strobe - Passed
Test A/C #7 Duct detector - Passed
North east break room added horn/strobe - Passed
West conference room added horn/strobe - Passed
North training room added horn/strobe in 2nd half - Passed
Floor 10 Elevator room needs horn/strobe, Added horn/strobe - Passed
Repair fire fighter phone, phone repaired - Passed
Floor 9 - Tested smoke detector in the returned air plenum - Passed
Tested elevator recall - Passed
Floor 8 - South file room strobe bad, horn/strobe replaced - Passed
Tested smoke detector in the returned air plenum - Passed
Tested elevator recall - Passed
Floor 7 - Tested smoke detector in the returned air plenum - Passed
Tested elevator recall - Passed
Floor 6 - Tested smoke detector in the returned air plenum - Passed
Tested elevator recall - Passed
Floor 5 - Tested smoke detector in the returned air plenum - Passed
Tested elevator recall - Passed
Floor 4 - No strobes, but vice worked, horn/strobes worked - Passed
Tested elevator recall - Passed
Ducts were tested on 06/13/2012 - Passed
Floor 3 - - Tested elevator recall - Passed
In generator room fire phone failed, phone repaired - Passed
Floor 2 - Stair well 3 need smoke detector on top, smoke added to top - Passed
Lobby floor - Passed
Parking level 1 - Tested okay & duct detector passed
Parking level 2 - Tested okay
Parking level 3 - Duct detector for A/C #6 passed (reported activation to FACP) but the A/C unit did not shut down therefore failed, tested A/C #6 again unit did shut down - Passed
Still need to test all tampers and flow switches
Still need to check signals for the fire pump operation
Still need to check signals for generator operations
Still need to do 24 hour stand-by battery test and 5 min run time
Still need to check on the operation of the smoke exhaust systems, fans failed to operate during testing (all stairwells).
06/13/2012 FIRE - ALARM FINAL Correction Required Floors 1-9 - Elevators fail to recall when system was set off
Floor 9 - Tested okay
Floor 8 - South file room strobe bad
Floor 7 - Tested okay
Floor 6 - Tested okay
Floor 5 - Tested okay
Floor 4 - No strobes, but vice worked.
Floor 3 - In generator room warren phone failed
Floor 2 - Stair well 3 need smoke detector on top
Floor 1 - Tested okay
Parking level 1 - Tested okay & duct detector passed
Parking level 2 - Tested okay
Parking level 3 - Duct detector for A/C 6 passed (reported activation to FACP) but the A/C unit did not shut down therefore failed
Floors 3 & 4 tested duct detectors passed
Still need to test duct detectors on upper floors
Still need to done 24 hour stand-by battery test
Still need to check on the operation of the smoke ventilation system
06/12/2012 FIRE - ALARM FINAL Correction Required All box phones failed in stairwells
Floor 10 Elevator room needs horn/strobe - repair fire fighter phone
Floor 11 Elevator room needs horn/strobe
North training room needs horn/strobe on other side of folding doors
Floor 12 - Okay
Floor 14 - West tenant space stairwell add smoke and horn/strobe (keep smoke 3 feet away from all exhaust and intake vents).
Floor 15 - West tenant space stairwell add smoke and horn/strobe (keep smoke 3 feet away from all exhaust and intake vents).
Floor 16 - West tenant space stairwell add smoke and horn/strobe (keep smoke 3 feet away from all exhaust and intake vents).
Floor 17 - Okay
Floor 18 - Okay
Floor 19 - Okay
Floor 20 - Box phones not working in stairwells
Floor 21 - Okay
Floor 22 - North hall need to add horn/strobe to quite
Floor 23 - Okay
Floor 24 - Need to turn up sounders to quite
Floor 25 - Top of stairs need to add a smoke
Still need to check out all duct detectors on the above floors listed
Need to check all stairwells venting or pressurization system?