Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2012 | FIRE SPKLR - FINAL | Approved | ||
| 04/17/2012 | FIRE SPKLR - FINAL | Denied | Over 12 heads on main floor covered with tape or painted need to change heads and remove tape. Uprights blocked by insulation by tanning rooms and by rear exit door eastside Correct upright coverage by hallway to rear exit door a pocket was made with a new full height wall added. Add sprinkler coverage per approved plans were water fountains are located. |