Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2012 | FIRE SPKLR - FINAL | Approved | Pump was re-tested for low grinding sound nothing sounded. | |
| 02/20/2012 | FIRE SPKLR - FINAL | Partial Approval | 1.) During Fire pump test motor has a low grinding sound coming from it; sound does go away but comes back will need to have this looked into. 2.) Need pump curve sent to me before clearing test as a final. 3.) Alarm panel showing tamper trouble but all valves are open need to check switches (Kazal adjusted switches no troubles) 4.) Alarm panel shows fire pump in trouble. (City electrician re-wired no troubles) 5.) Shut power switch off to the fire pump trouble was received at the alarm panel. 6.) Tested fire pump one more time received at panel. 7.) I advised Wayne from city that they can cancel fire watch. Fire pump up and running and fire alarm panel all clear. |