Permit: T12BU00011

Parcel: 117132170

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
02/16/2012 FIRE SPKLR - FINAL Approved
02/09/2012 FIRE SPKLR - FINAL Denied Sprinkler head placement below mezzanine is correct except for one head needs to be lowered to 1 inch below metal beam.
Discovered problems with upright heads near ceiling:
5 painted sprinkler heads
1 bent sprinkler head.
1 head needs to be raised above obstruction