Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2012 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 02/22/2012 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1) PROVIDE ACCESS INSIDE 2) NOTE: 30 CALL AHEAD PROVIDED 3) SINGLE WALL MAY NOT BE USED AFTER TYPE B AND ALSO NOT OUTSIDE 4) EXTEND B VENT TO TERMINATE |
|
| 02/17/2012 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE FULL SIZED PIPING 2) PROVIDE A SEPERATE VALVE FOR EACH 3) PROVIDE PROPER VENTING INSTALLED PER MANUFACTURER INSTRUCTIONS 3) TERMINATE ABOVE COOLER |
|
| 02/08/2012 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* ETA AND 10 MINUTE CALL PROVIDED PROVIDE MIN 3/4" PIPING TO SECURE BOTH WH & FURNACE SECURE VENT CONNECTORS W/SCREWS PROVIDE MIN 1" CLEARANCE AROUND B VENT PROVIDE ELECTRICAL BONDING YARD OK |