Permit: T11PL02033

Parcel: 131100510


Addresses:

5518 E JUAREZ ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/28/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
12/21/2011 PLUMBING - FINAL Cancelled CANCELLED PER OWNER HEATH #304-5307
12/20/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) OFF SET PIPING AT ROOF LEVEL, USE ? ROOF FLASHING
2) USE RED WOOD WITH GALV 2 HOLE CLAMPS
3) CONNECT 3" SINGLE WALL TO B-VENT PROPERLY, SECURE WITH GALV SCREWS
4) PROVIDE CLEARANCE
5) REPLACE RELIFE VALVE
6) TEST ENTIRE SYSTEM
12/14/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) POST YOUR ADDRESS
2) COMPLETE OK, CONNECT FURNACE SUPPLY TO 1"
3) INSTALL WATER HEATER
4) TRACER WIRE REQUIRE AT YARD 18" COVER ABOVE PE