Permit: T11PL01919

Parcel: 130191280


Addresses:

4611 E 31ST ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/08/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THERE IS NO PRESSURE IN THE GAS LINE
2) USE ONLY APPROVED PIPE WRAP TAPE ON FITTINGS AND TOOL MARKS. YOU CANNOT USE ELECTRICAL TAPE. USE APPROVED TAPE PRIMER PRIOR TO TAPING FITTINGS
11/23/2011 PLUMBING - FINAL Denied TEST TO BE ON ENTIRE GAS PIPING SYSTEM HOLDING A MINIMUM 10 PSI FOR 15 MINUTES WITH NO LOSS OF PRESSURE.
PROVIDE PIPE TAPE PRIMER THEN PIPE TAPE ALL TOOL MARKS & FITTINGS UNDERGROUND. PROVIDE FIRM BEDDING FOR ALL UNDERGROUND PIPING.
PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES
WATER HEATER VENT TO BE INSTALLEC CORRECTLY WITH APPROVED MATERIALS & FITTINGS AND APPROVED PLUG FOR UNUSED WYE FITING WITH FASTENERS AT ALL VENT JOINTS.