Permit: T11PL01720

Parcel: 132170900


Addresses:

1202 E MICHIGAN ST

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/21/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE CORRECT BLDG GROUND FOR ELECTRIC SYSTEM
2) PROVIDE BONDING PER NOTE #2 10/19/11 AND SEE NOTE #4 FOR CORRECT FURNACE VENTING
10/19/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PRIME THEN TAPE ALL NEW AND EXPOSED UNDERGROUND FITTINGS & TOOL MARKS ON PIPING
2) PROVIDE BONDING OF BLDG GAS SYSTEM
3) PROVIDE APPROVED GAS SHUT OFF VALVES AT FURNACE & DRYER LOCATION
4) PROVIDE APPROVED VENTING SYSTEM FOR FURNACE, NO TAPE ON VENT CONNECTOR JOINTS, ALL JOINTS MADE UP CORRECTLY DBL WALL VENT THRU CEILING AND ROOF PROPERLY FLASHED ON ROOF TOP WITH DBLE WALL VENT TO TERMINATION AT APPROVED VENT CAP EXTENDING TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE