Permit: T11PL01700

Parcel: 130102100


Addresses:

3101 E 28TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/24/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
10/21/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) GAS CARD AT METER
10/20/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST TO HAVE MINIMUM 10 PSI IN ENTIRE SYSTEM AND HOLD FOR 15 MINUTES WITH NO LOSS OF PRESSURE
2) ROOF FLASHING TO BE MADE WEATHER TIGHT AT ROOF
3) VENTS FROM WATER HEATER AND FURNACE WITHIN 10' OF COOLER INTAKE TO BE MINIMUM 3' ABOVE TOP OF COOLER INTAKE WITH APPROVED DBL WALL VENT PIPING AND CAP
4) SECURE GAS PIPE IN FURNACE CLOSET
5) PROVIDE AN APPROVED VENT SYSTEM FOR WATER HEATER
6) SECURE GAS PIPE AT WATER HEATER AND PROVIDE CLEARANCE FROM PIPT OT REMOVE WATER HEATER
7) PROVIDE AN APPROVED WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING SYSTEM
10/19/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) YARDLINE OK; REMOVE BRICKS PRIOR TO COVERING
2) CORRECT UNSANITARY SEWER CLEANOUT
3) CORRECT B-VENT OF WATER HEATER; UPSIDE DOWN AND EXTEND ABOVE COOLER
4) SECURE VENT CONNECTIONS WITH SCREWS
10/17/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*