Permit: T11PL01655

Parcel: 135021890

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/07/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL VENT FITTINGS IN THE CORRECT DIRECTION OF FLOW
2) SECURE VENT CONNECTIONS WITH GALV SCREWS AND REMOVE TAPE
3) HARD PIPE RELIEF WITHOUT TRAPS OR RESTRICTIONS
4) REMOVE BK IRON NIPPLE AND USE APPROVED PIPING FOR WATER
5) INSTALL SEDIMENT TRAP ON GAS SUPPLY
6) OK TO TURN ON AFTER REPAIRING