Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CORRECT CW RISER AS NOTED 2) STEEL MALE PIPE THREADS MAY NOT BE USED WITH PLASTIC FEMALE THREADS 3) PROVIDE A CODE APPROVED TRANSITION FITTING OF FLEX CONNECTOR |
|
| 09/22/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE B VENT TRANSITION ADAPTOR AND CONNECT VENT AND DRAFT HOOD PROPERLY 2) PROVIDE THE MINIMUM REQUIRED CLEARANCE AROUND BO VENT AT ROOF PENETRATION 3) COPPER MAY NOT BE DIRETLY CONNECTED TO GALVANIZED WITHOUT DIELECTRIC OR BRASS SEPERATION 4) 1/2" PEX IS UNDERSIZED AND NOT PROPERLY INSTALLED 5) 3/4 REPAIR COUPLING ON SUPPLY RISER MAY NOT BE USED WITHOUT RESTRAINT 6) PROVIDE A SOLID PIPE CONNECTION 7) SUPPORT/SECURE GAS SUPPLY PIPE |