Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) TEN POUND TEST TO BE IN PLACE WHEN THE INSPECTOR ARRIVES 2) IT APPEARS THAT THE TEMPERATURE AND PRESSURE RELIEF DRAIN IS LEAKING, IF SO THE VALVE WILL HAVE TO BE REPLACED 3) CORRECTIONS MADE OK FROM 10/05/11 4) CHANGE T & P VALVE 5) EXTEND VENT-3 SHEET METAL SCREWS AT EACH SINGLE WALL JOINT |
|
| 10/05/2011 | PLUMBING - FINAL | Not ready for Inspection | CORRECT SAGGIN FLOOR UNDER WATER HEATER. WH RELIEF VALVE AND DRAINING PIPING MAY NOT BE TRAPPED - USE HARD PIPE. CORRECT VENT USE PROPER INCREASERS OR PIPE 3" TYPE B, THROUGH 6" ABANDON FURNACE VENT. OK TO COVER YARD PIPING. |
|
| 10/04/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PE REQUIRES 18" OF COVER, YOUR LINE IS ONLY 12"-13" DROP 2) A TEST ON THE ENTIRE SYSTEM IS REQUIRED, PROVIDE ACCESS |