Permit: T11PL01569

Parcel: 125111130


Addresses:

3618 E 2ND ST #06

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/11/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
1) 15 PSI TEST IS OK
2) LEFT GAS CARD
10/08/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) ALL ROCKS TO BE REMOVED FROM TRENCH
2) MAKE SURE B-VENT IS INSTALLED CORRECTLY
3) REQUIRE 1" CLEARANCE FROM COMBUSTIBLES
4) REQUIRE SHUT OFF AT WALL FURNACE
5) LEFT GAS CARD
09/28/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSE ALL NEW GAS PIPE
2) BURIED GAS PIPE MUST BE SCOTCH COATED PIPE
3) ALL FITTINGS AND TOOL MARKS MUST BE PRIMERED AND TAPED WITH 40 MILS OF TAPE
4) TAPES AND PRIMERS MUST BE UPC APPROVED
5) USE APPROVED GAS SHUT OFF VALVES FOR ALL APPLIANCES
6) VENT PIPE ON WATER HEATER IS UPSIDE DOWN
7) PROVIDE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES
8) RECOMMEND USING A LICENSED CONTRACTOR