Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) 15 PSI TEST IS OK 2) LEFT GAS CARD |
|
| 10/08/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL ROCKS TO BE REMOVED FROM TRENCH 2) MAKE SURE B-VENT IS INSTALLED CORRECTLY 3) REQUIRE 1" CLEARANCE FROM COMBUSTIBLES 4) REQUIRE SHUT OFF AT WALL FURNACE 5) LEFT GAS CARD |
|
| 09/28/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE ALL NEW GAS PIPE 2) BURIED GAS PIPE MUST BE SCOTCH COATED PIPE 3) ALL FITTINGS AND TOOL MARKS MUST BE PRIMERED AND TAPED WITH 40 MILS OF TAPE 4) TAPES AND PRIMERS MUST BE UPC APPROVED 5) USE APPROVED GAS SHUT OFF VALVES FOR ALL APPLIANCES 6) VENT PIPE ON WATER HEATER IS UPSIDE DOWN 7) PROVIDE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES 8) RECOMMEND USING A LICENSED CONTRACTOR |