Permit: T11PL01549

Parcel: 122091260

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/22/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
09/21/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) 15 PSI TEST IS OK
2) RE-INSTALL VENTING TO WATER HEATER
3) DO NOT USE SINGLE WALL VENTING OUTDOORS
4) PROVIDE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES
5) SECURE VENT WITH A VENT PIPE HANGER, NOT WIRE
6) PROVIDE ELECTRICAL BOND TO GAS PIPING
7) OK TO INSTALL ENCLOSURE AT WATER HEATER
8) RECALL FOR FINAL
09/20/2011 PLUMBING - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME