Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/22/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CORRECT WATER HEATER HOOD, INSTALL TYPE B VENT 2) HOT SIDE STILL HAS UNAPPROVED BLACK IRON FITTINGS 3) OK FOR GAS, RECALL FOR FINAL APPROVAL |
|
| 09/16/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*. 1) POST YOUR ADDRESS PLEASE 2) YOUR TEST GAUGE HAS LOST PRESSURE, CHECK FOR LEAKS AND CORRECT. REQUIRED 10 PSI 3) PROVIDE A TYPE B VENTING FOR WATER HEATER 4) PROVIDE AN OPERATIONAL RELIEF VALVE WITH PROPER TERMINATION 5) REMOVE BLK IRONG NIPPLE AND PLUG FROM WATER SUPPLY 6) FLARED JOINTS SHALL NOT HAVE TELFON TAPE 7) SHORTEN AND SUPPORT GAS BRANCH TO WATER HEATER 8) INSTALL SEDIMENT TRAP AFTER SHUT OFF VALVE 9) PROVIDE A PERMIT FOR NEW WATER HEATER IN UNIT #1 (NORTH) |