Permit: T11PL01534

Parcel: 122180540


Addresses:

1626 N DODGE BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/12/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/05/2011 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL WORK MUST BE COMPLETE BEFORE FINAL
WATER HEATERS TO BE PROTECTED FROM ELEMENTS
ALL VENTS TO BE RUN
ALL WATER PIPING TO BE COMPLETE
WATER HEATER INSTALLATION TO BE COMPLETE
EXTERIOR WALL PENETRATIONS SEALED
PROVIDE SAFE ACCESS TO ROOF
PROVIDE ACCESS TO INSIDE RESIDENCES
SEDIMENT TRAPS MAY NOT EXTEND TO CONCRETE
3/4" GAS TO EXTEND TO WATER HEATER AT GUEST HOUSE

WHERE IS PERMIT FOR NEW YARDWATER PIPING AND WHO INSPECTED IT?

THIS MAY NOT BE A COMPLETE LIST
CONTINUED NOT READY MAY RESULT IN REINSPECTION FEE
09/29/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) OK TO COVER UNDERGROUND PIPE
09/27/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) GAS LINE TO GUEST HOUSE TO HAVE TRACER WIRE
2) THIS PERMIT IS FOR METER RELOCATE
3) WHERE IS THE GAS PIPING TO THE BLDG ?
4) UNIONS ARE NOT DESIGNED TO BE SEALED WITH PIPE ? OR TEFLON TAPE ON THE UNION THREADS
5) USE A 15 POUND GAUGE WITH 1/10 POUND INCREMENTATION