Permit: T11PL01518

Parcel: 134241420


Addresses:

625 S HARVARD AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/27/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
09/15/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 10 PSI TEST NOT HOLDING
2) PROVIDE REDWOOD OR PRESSURE TREATED WOOD FOR PIPE SUPPORTS ON ROOF
3) CLAMP GAS LINE TO BLOCKS
4) EXTEND T & P DRAIN DOWN INTO PAN
5) NO THREADS ALLOWED ON END OF PIPE
6) RECONNECT FURNACE VENT CONNECTOR
7) EXTEND WATER HEATER VENTS MINIMUM 3' ABOVE EVAP COOLERS
8) REMOVE OLD GAS RISER
9) REMOVE TEE IN GAS LINE ABOVE OLD RISER
10) PROVIDE A WORKING T & P RELIEF VALVE AT WATER HEATERS