Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2011 | PLUMBING - ROOF DRAINS | Approved | IVRS - Inspection :* | |
| 10/31/2011 | PLUMBING - ROOF DRAINS | Not ready for Inspection | 1) CHAPTER 11 REQUIRES THAT RAIN WATER LEADER FITTINGS BE DRAINAGE TYPE 2) PRESSURE FITTINGS NOT PERMITTED AND EPOXY NOT PERMITTED FOR REPAIRS 3) REVISE PLAN TO SHOW 8" X 6" REDUCER AT ? TO EXISTING |
|
| 10/28/2011 | PLUMBING - ROOF DRAINS | Denied | 1) NOTIFIED LINCOLN 30 MINUTES AHEAD 2) NO PLAN/PERMIT ON SITE 3) RAIN WATER FITTINGS TO BE DRAINAGE TYPE 4) HOW IS PIPE TO BE PROTECTED FROM UV RAYS ? NOTE: PAINTING IS LIMITED TO VENT TERMINALS 5) CLEANOUT TO BE AT THE BASE OF THE RISER (STACK) 6) EPOXY NOT APPROVED FOR LEAK REPAIR 7) NUMBEROUS LEAKS ON PIPE 8) UNABLE TO TELL HOW CONNECTION IS MADE BETWEEN ROFO DRAIN AND OUTLET AND SCHEDULE 80 PVC |
|
| 10/20/2011 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/08/2011 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/04/2011 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* PROVIDE A WATER TEST ON THIS RAW DRAIN TO 5' BLD EXTERIOR, REVISE THIS PLAN TO SHOW 8" PIPING REDUCING TO 6" AT C/O FITTING |