Permit: T11PL01500

Parcel: 12412293A


Addresses:

301 S PARK AV


Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T11PL01500

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
11/04/2011 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
10/31/2011 PLUMBING - ROOF DRAINS Not ready for Inspection 1) CHAPTER 11 REQUIRES THAT RAIN WATER LEADER FITTINGS BE DRAINAGE TYPE
2) PRESSURE FITTINGS NOT PERMITTED AND EPOXY NOT PERMITTED FOR REPAIRS
3) REVISE PLAN TO SHOW 8" X 6" REDUCER AT ? TO EXISTING
10/28/2011 PLUMBING - ROOF DRAINS Denied 1) NOTIFIED LINCOLN 30 MINUTES AHEAD
2) NO PLAN/PERMIT ON SITE
3) RAIN WATER FITTINGS TO BE DRAINAGE TYPE
4) HOW IS PIPE TO BE PROTECTED FROM UV RAYS ? NOTE: PAINTING IS LIMITED TO VENT TERMINALS
5) CLEANOUT TO BE AT THE BASE OF THE RISER (STACK)
6) EPOXY NOT APPROVED FOR LEAK REPAIR
7) NUMBEROUS LEAKS ON PIPE
8) UNABLE TO TELL HOW CONNECTION IS MADE BETWEEN ROFO DRAIN AND OUTLET AND SCHEDULE 80 PVC
10/20/2011 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
10/08/2011 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
10/04/2011 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
PROVIDE A WATER TEST ON THIS RAW DRAIN TO 5' BLD EXTERIOR, REVISE THIS PLAN TO SHOW 8" PIPING REDUCING TO 6" AT C/O FITTING