Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2011 | PLUMBING - FINAL | Approved | ||
| 09/13/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 15 PSI TEST OK 2) IN ORDER TO GET THE GAS CLEARANCE CARD YOU WILL NEED TO PROVIDE A PERMIT FOR THE NEW A/C, FURNACE AND WATER HEATER. THE WATER HEATER WILL PASS INSPECTION, HOWEVER THE FURNACE WILL NEED A HOSE CLAMP ON CONDENSATE PUMP DISCHARGE 2) TERMINATE 3/8" DRAIN HOSE INTO THE HORIZONTAL SECTION OF THE CONDENSATE DRAIN LINE WHICH WILL NEED TO BE INCREASED TO 3/4" 3) USE LISTED OUTDOOR TAPE ON THE EXPOSED ARMAFLEX ON THE ROOF 4) EXTEND THE FURNACE VENT MINIMUM 3' ABOVE THE COMBUSTION AIR INTAKE 5) PROVIDE THE REQUIRED DRAWING FOR NEW A/C UNIT ON THE ROOF 6) PROVIDE ACCESS TO THE ROOF FOR INSPECTION 7) TERMINATE THE CONDENSATE DRAIN WITH AN ELBOW AT END OF DISCHARGE AND A NIPPLE TO DIVERT THE WATER AWAY FROM THE HOUSE |