Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/12/2011 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A PERMIT FOR NEW FURNACE AND A/C 2) PROBVIDE A SECONDARY OVERFLOW SENSOR ON COIL 3) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 4) EXPOSED T-STAT WIRE MUST BE PROTECTED FROM DAMAGE 5) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR 6) OK TO BACKFILL TRENCH-DO NOT HAVE ANY STONES IN THE BACKFILL 7) 11 PSI TEST IS OK 8) LEFT GAS CARD 9) RESCHEDULE AFTER MECHANICAL PERMIT IS OBTAINED |