Permit: T11PL01440

Parcel: 12611157A


Addresses:

4445 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/16/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/01/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
08/31/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) 10 PSI TEST FROM METER THRU TO (1) ROOF TOP UNIT
2) (2) SHUT OFF VALVES AT METER HAVE PIPING UP TO ROOF LEVEL THIS TESTED TO VALVE ONLY, SECURE OR CAP AT VALVES
3) TEST CONTINOUS THRU TO VALVE PRIOR TO ANSUL VALVE ONLY AND TO 3/4" PIPING TO NEW WATER HEATER
4) APPROVED PLAN SHOW 1" TO THIS UNIT, REVISE APPROVED PLAN WITH BTU'S AT EACH APPLIANCE FOR CORRECT SIZING WITH ADDITION OF 199,000 BTU DEVICE
5) WATER HEATER WILL ALLOW 2 PSI TEST WITH TEST GAUGE IN 1/10 POUND INCREMENTS THRU ANSUL VALVE TO COOKING LINE SHUT OFF VALVES
6) PROVIDE ROOF TOP ACCESS