| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/25/2011 | PLUMBING - FINAL | Not ready for Inspection | TYPE B VENT REQUIRED TO TERMINATION W/ 1" CLEARANCE AT ROOF. PROVIDE A 10 PSI TEST SECURE ALL SIDES OF FLASHING PIPING AWAY MAY NOT TOUCH ROOF AFTER TEE TO WH ELECTRICAL PANEL COVER & CONDENSATE FOR MATT |
|
| 08/22/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/15/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) EXTEND RELIEF DRAIN TO EXTERIOR 2) MAKE UP JOINTS ON B-VENT AND PROVIDE MINIMUM 1" CLEARANCE AT ROOF PENETRATION 3) PROVIDE AN APPROVED METAL VENT FLASHING AND REMOVE SINGLE WALL ABOVE ROOF 4) PROVIDE FLASHINGS AT ALL ROOF PENETRATIONS 5) PROVIDE CLEARANCE ABOVE ROOF, WEATHER RESISTANT SUPPORTS 6) SUPPORT FURNACE BRANCH 7) PROVIDE PERMIT FOR NEW FURNACE (MECHANICAL) 8) PROVIDE SAFE ACCESS TO ROOF |
|
| 08/11/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED 12:54 PM |