Permit: T11PL01333

Parcel: 132091600

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/22/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
09/19/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PE REQUIRES 18" OF COVER
2) 10 PSI AIR PRESSURE REQUIRED FOR TEST
3) TYPE B VENTING REQUIRED OUTDOORS
4) 1 SOLID PLATFORM FOR WATER HEATER SUPPORT
08/11/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSE NEW YARD PIPING FOR INSPECTION
2) TEST WITH APPROVED GAUGE (1/10 PSI INCREMENTATIONS)
3) CORRECT FURNACE B-VENT, INSTALL IN CORRECT DIRECTION OF FLOW
4) INSTALL WATER HEATER ON AN APPROVED BASE
5) INSTALL CORRECTLY SIZED TYPE B-VENT
6) CHECK RELIEF VAVLE
7) IS THERE A PLAN/PEMIT ON SITE ?