Permit: T11PL01332

Parcel: 135061990

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
08/16/2011 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
08/15/2011 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) OK TO COVER METER TO 12' FROM BLDG
2) VERIFY (2) GROUND RODS AND REATTACH THE GROUND WIRE TO BOND THE BLDG WATER PIPING WITH A BONDING CLAMP, IF ONLY 1 GROUND ROD PROVIDE MINIMUM 10' METALLIC PIPEING IN GROUND AND REATTACH THE GROUND WIRE TO THE BLDG WATER PIPING SIDE WITH A BONDING CLAMP AND PROVIDE ANOTHER BONDING CLAMP ON BOTH SIDES OF DIELECTRIC UNION WITH A SOLID #4 OR #6 WIRE BETWEEN THOSE (2) BONDING CLAMPS AS A DIELECTRIC JUMPER UNION. VERIFY (2) OTHER WIRES NEED TO BE REATTACHED