Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2011 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 08/15/2011 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) OK TO COVER METER TO 12' FROM BLDG 2) VERIFY (2) GROUND RODS AND REATTACH THE GROUND WIRE TO BOND THE BLDG WATER PIPING WITH A BONDING CLAMP, IF ONLY 1 GROUND ROD PROVIDE MINIMUM 10' METALLIC PIPEING IN GROUND AND REATTACH THE GROUND WIRE TO THE BLDG WATER PIPING SIDE WITH A BONDING CLAMP AND PROVIDE ANOTHER BONDING CLAMP ON BOTH SIDES OF DIELECTRIC UNION WITH A SOLID #4 OR #6 WIRE BETWEEN THOSE (2) BONDING CLAMPS AS A DIELECTRIC JUMPER UNION. VERIFY (2) OTHER WIRES NEED TO BE REATTACHED |