Permit: T11PL01271

Parcel: 136212110


Addresses:

7412 E 38TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/03/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
08/02/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) REMOVE THE FUTURE TEE CONNECTION OR PROVIDE PLAN FOR ITS USE
2) TEST TO HOLD WITH NO LOSS OF PRESSURE
3) BLACK FITTINGS TO BE PRIMED WITH PIPE TAPE PRIMER, THEN WRAPPED WITH PIPE TAPE WRAP TO ACHIEVE 40 MIL THICKNESS OF WRAP
4) PROVIDE AN APPROVED ROOF FLASHING WHERE PIPE PENETRATIONS THRU ROOF
5) ARRANGE PIPING IN CLOSET SO DOOR CLOSES WITHOUT HITTING PIPING AND SO BOTH APPLIANCES CAN BE REMOVED WITHOUT PIPE DIS-ASSEMBLY
6) PROVIDE BONDING OF GAS SYSTEM
07/29/2011 PLUMBING - FINAL Cancelled CANCELLED PER OWNER BRETT #548-5023
07/29/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*