Permit: T11PL01269

Parcel: 132110460

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/04/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
08/03/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) THIS INSPECTION IS FOR 2223 E. MONTEREY:
REQUIRE: CONNECT VENT, WATER TAPE JOINTS AND INSTALL FLEX
2) RECALL FOR 2225
08/02/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/01/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TEST TO HOLD WITH NO LOSS OF PRESSURE FOR 15 MINUTES
2) INSTALL WATER HEATER VENT IN CORRECT DIRECTION OF FLOW
NOTES FOR 2225 E. MONTEREY VISTA:
1) TEST TO HOLD WITH NO LOSS OF PRESSURE FOR 15 MINUTES
2) FURNACE VENT TO BE INSTALLED, WITH NO TAPE AT VENT JOINT AND PROVIDE FASTENERS AT VENT JOINTS
3) INSTALL WATER HEATER VENT IN CORRECT DIRECTION OF FLOW
07/29/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) REQUIRE A MINIMUM 10 POUND TEST AT TIME OF INSPECTION
2) ALL VALVES TO BE AGA OR CSA APPROVED
3) ALL PIPING COVERED WITHOUT INSPECTION
4) NO BLACK IRON PIPE PERMITTED UNDERGROUND
5) DUCT TAPE NOT PERMITTED ON FLUE PIPING-USE NO TAPE, MAKE UP JOINT AND USE 3 SHEET METAL SCREWS
6) AT 2225 COLD INLET REQUIRES SHUT OFF