Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T11PL01168
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
10/08/2011 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAY NOT INTERMINGLE ABS AND PCV 2) VERTICAL AND HORIZONTAL CHANGE OF DIRECTION TO BE BE A SWEEP 3) VENT FITTINGS BELOW THE FLOOD RIM TO BE DRAINAGE TYPE 4) BLAKE TESS USED UNDER SLAB MAYBE USED THIS TIME (ONLY) 5) WLL ACCEPT FLOW TEST-CHECK GRADE ON PIPE 6) |
|
10/07/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED PLANS AND ACCESS 2) PAY ATTENTION TO UPC CODE REQUIREMENTS AND MANUFACTURERS INSTALLATION INSTRUCTIONS 3) TAKE PRECAUTIONS TO KEEP SEWER GASES FROM ESCAPING IN THIS OPEN RESTAURANT |