Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11PL01082
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
07/01/2011 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) 14 PSI TEST OK 2) 3/8" I.D. X 60" GAS FLEX NOT ADEQUATE FOR 65,000 BTU 3) PROVIDE CLEAN FILL DIRT OR HAVE A SIFTER ON SITE4) REMOVE ALL STONEY DIRT FROM TRENCH 4) RECALL FOR FINAL |