Permit: T11PL01063

Parcel: 120060970


Addresses:

213 E LINCOLN ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/18/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
07/11/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL ITEMS ABOVE
06/30/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SUPPORTS FOR PIPING AT ALL LOCATIONS
2) SEAL PIPE PENETRATIONS INTO BLDG
3) VENT PIPING FOR WATER HEATER TO BE ATTACHED TO DRAFT HOOD AND HAVE FASTENERS AT VENT JOINTS
4) WATER HEATER TO SIT ON FIRM FOUNDATION
5) T & P DRAIN TO GRAVITY DRAIN TO DAY LIGHT TERMINATING 90 DEGREE DOWN 6" TO 24" FROM FINISH GRADE
6) EXTEND FURNACE VENT TO 3' ABOVE TOP OF INTAKE WHEN WITHIN 10'
7) PROVIDE BONDING OF BLDG GAS