Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ABS REQUIRES A MINIMUM OF 12" OF COVER. LESS THAN 12" OF COVER USE CAST IRON 2) TRACER WIRE COLOR FOR SEWER IS GREEN, NOT BLUE 3) REQUIRE A MINIMUM OF 1 PERCENT SLOPE 4) CONTRACTOR TO PAY REINSPECTION FEE 5) PROVIDE EVIDENCE THAT SEPTIC TANK HAS BEEN PUMPED AND BROKEN |
|
| 06/14/2011 | PLUMBING - FINAL | Denied | 1) FAILURE TO COMPLY WITH PREVIOUSLY NOTED ITEMS WILL RESULT IN A REINSPECTION FEES. INSPECTION HISTORY SHALL BE ON SITE AT AL TIMES | |
| 06/13/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) UNIT NO MUMBERED CORRECTLY 2) UNABLE TO LOCATE PLAN OR PERMIT 3) COULDN'T FIND SEPTIC TANK 4) TANK TO BE PUMPED, BROKEN, INSPECTED AND REFILLED 5) ABS REQUIRES A MINIMUM OF 12" OF COVER 6) PIPING LESS THAN 12" DEEP TO BE APPROVED MATERIAL |