Permit: T11PL00970

Parcel: 126040680


Addresses:

730 N CATALINA AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/13/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
06/09/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PSI DOWN TO 4, MINIMUM 10 PSI REQUIRED
2) REMOVE THE TAPE COVERING THE FITTINGS INSTALLED ABOVE GRADE
3) PIPING SHOULD NOT HAVE BEEN PAINTED
4) PROPERLY INSTALLED FLASHINGS ARE REQUIRED AT ALL ROOF PENETRATIONS
5) WEATHER RESISTANT PIPE SUPPORTS REQUIRED
6) PIPING MAY NOT BE STRAINED
7) COUNTER FLASHING NEEDED AT B VENT PENETRATION
8) CORRECT FURNACE VENT CONNECTOR TO B VENT
9) INSTALL SEDIMENT TRAPS AT FURNACE AND WATER HEATER
10) SECURE VENTS WITH SCREWS
11) PROVIDE AN OPERATION RELIFE VALVE
12) SUPPORT PIPE AS CLOSE AS POSSIBLE TO SOV
13) PROVIDE ELECTRICAL BONDING