Permit: T11PL00880

Parcel: 114474810


Addresses:

3031 N RIO VERDE DR

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
05/17/2011 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
05/16/2011 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1' COVER REQUIRED, OFFSET DOWN ON OTHER SIDE OF CONCRETE IF YOU ARE UNABLE TO TUNNEL AT THAT ELEVATION
2) COMPLETE VACUUM BREAKER INSTALLATION AND SEAL WALL PENETRATION
3) CORRECT SIZING RESTRICTION AT IRR ASSEMBLY
4) PROVIDE BACKFLOW CERT
5) SUPPORT PEX ABOVE CEILING AND PROVIDE ACCESS TO INSPECT WORK ABOVE CEILING
6) REVISE PLAN TO SHOW THIS INSTALLATION