Permit: T11PL00851

Parcel: 136381650


Addresses:

4743 S PRIMROSE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/16/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
1) GAS TO ONLY WATER HEATER AND ROOF TOP UNIT
05/12/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE KEY FOR FIREPLACE TO VERIFY TEST INTO HEARTH
2) PROVIDE CORRECT RATED BTU FLEX TO ROOF TOP UNIT
3) BLOCKING ON ROOF TO BE IN CONTACT WITH ROOF, BLOCKING TO BE MASTIC TO ROOF
4) REMOVE ALL TAPE FROM WATER HEATER CONNECTORS, PROVIDE FASTENERS AT EACH JOINT
5) BOND TO BE MINIMUM #6 WIRE
6) PROVIDE KEY TO BACK GATE, TO ALLEY. FAILURE TO BE READY AT INSPECTION WILL RESULT IN REINSPECTION FEE AT FUTURE INSPECTION