Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* TYPE B VENT REQURIES MIN 1" CLEARANCE (ATTIC) CORRECT FURNANCE VENT, IT HAS COME APART. ALSO SEACURE WH VENT W/GALV SCREWS. FLEX NOT APPROVED ON RELIEF DRAIN. REPLACE SEIZED UP RELIEF VALVE SUDIMENT TRAPS REQUIRED SLECTRUST BONDING REQ A PERMIT OR VACUUM BREAKER IS REQUIRED GR VALVE REPLACEMENT (HOSE BIB) |
|
| 05/09/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ARE BOTH UNITS SUPPLIED WITH ONE METER ? 2) DID YOU REPLACE THE PIPING AS DESCRIBED ? IF SO A PLAN IS REQUIRED 3) PROVIDE ACCESS TO ALL GAS APPLIANCES ON THIS SYSTEM 4) TEST WITH A 15 PSI GAUGE 5) NEW HOSE BIB REQUIRES A VACUUM BREAKER |