Permit: T11PL00732

Parcel: 113093920

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11PL00732

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) ABS DWV, PEX OK-OK TO COVER
05/17/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) WASHER TRAP TO HIGH
05/13/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) MINIMUM SIZE WASTE FOR WASHER TO BE 2" WASHER REQUIRES A VENT
2) SANTEE ON IT'S BACK IS NOT A DRAINAGE FITTING. USE A COMBO. HOW ARE SINKS TO BE VENTED ?
3) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP
4) WATER TEST REQUIRED
5) SEWER OK TO COVER