Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/17/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT B: 1) WOOD PLATFORM REQUIRES A PAN OR REMOVE PLATFORM 2) CORRECT LEAKS ON RELIEF DRAIN PIPING AND SUPPLY FLEX CONNECTIONS, ALSO T & P LEAKING 3) REMOVE TAPE CONCEALING VENT GAS LEAK. PROVIDE PROPER MAKE UP ON ALL FITTINGS. SECURE WITH GALV SCREWS 4) REPLACE LEAKING SHUT OFF VALVE WITH A FULL PORT VALVE 5) INSTALL A SEDIMENT TRAP ON GAS SUPPLY UNIT C: 1) SAME CORRECTIONS AND IMPROPER USE OF REPAIR COUPLING UPSTREAM OF SOV 2) TYPE B VENT IS UPSIDE DOWN NOTE: HOSE BIBS REQUIRE VACUUM BREAKERS |