Permit: T11PL00715

Parcel: 121020760


Addresses:

5657 E PIMA ST #01

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/09/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
05/17/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT B:
1) WOOD PLATFORM REQUIRES A PAN OR REMOVE PLATFORM
2) CORRECT LEAKS ON RELIEF DRAIN PIPING AND SUPPLY FLEX CONNECTIONS, ALSO T & P LEAKING
3) REMOVE TAPE CONCEALING VENT GAS LEAK. PROVIDE PROPER MAKE UP ON ALL FITTINGS. SECURE WITH GALV SCREWS
4) REPLACE LEAKING SHUT OFF VALVE WITH A FULL PORT VALVE
5) INSTALL A SEDIMENT TRAP ON GAS SUPPLY
UNIT C:
1) SAME CORRECTIONS AND IMPROPER USE OF REPAIR COUPLING UPSTREAM OF SOV
2) TYPE B VENT IS UPSIDE DOWN
NOTE: HOSE BIBS REQUIRE VACUUM BREAKERS