Permit: T11PL00603

Parcel: 13811055F

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T11PL00603

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
04/07/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/05/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/30/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE THE GAS SHUT OFF VALVE & MOBILE HOME FLEX AT THE PIPING AT METER LOCATION AND RETEST GAS SYSTEM
2) THE FLOOR OF THE WATER HEATER AREA APPEARS TO BE SEVERLY DAMAGED FROM WATER, PROVIDE PROOF OF STRUCTURAL SUPPORT FOR WATER HEATER OR REINFORCE THE WATER HEATER FLOOR
3) TEST TO HOLD FOR 15 MINUTES WITH NO LOSS OF PRESSURE
4) REMOVE THE PIPE TO PIPE SUPPORT ON GAS PIPING AND SUPPORT TO STRUCTURE ALL GAS PIPING