Permit: T11PL00508

Parcel: 12009309B


Addresses:

401 E IRVINGTON RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/30/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
03/21/2011 PLUMBING - FINAL Not ready for Inspection 1. 60 PSI TEST IS OK FOR USE ONLY WITH FUEL TRAIN REGULATOR INSTALLED PENDING INFORMATION FROM MANUFACTURER. 2. PLEASE HAVE FACTORY INSTALLATION INSTRUCTIONS ON SITE FOR CORRECT VENTING OF THIS APPLIANCE. 3. PROVIDE INFORMATION ON FUEL TRAIN REGULATOR TO BE COMPATIBLE WITH 2 PSI TO APPLIANCE USE OF 5.5 INCHES TO 14 INCHES WATER COLUMN. 4. REGULATOR NEEDS VENT TO EXTERIOR OF BUILDING FULL SIZED APPROVED PIPING FROM REGULATOR VENT OUTLET TO WEATHER 90 DEGREE WITH SCREEN IN TERMINATION.