Permit: T11PL00482

Parcel: 11462011D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/12/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
1) REMOVE ROCKS AND DEBRIS FROM DITCH AND BACK FILL WITH 1/2" MINUS MATERIAL
05/10/2011 PLUMBING - FINAL Cancelled CANCELED PER ALICIA OF TRIUMPH AIR #408-7444
03/25/2011 PLUMBING - FINAL Denied GAS IS DISCONNECTED FROM FIREPLACE ON ROOF AND NOT TESTED INTO HEARTH, DO NOT RECONNECT WITHOUT REINSPECTION, PROPERLY SUPPORT GAS PIPING ACROSS ROOFAT CORRECT INTERVALS WITH BLOCKING MASTIC TO ROOF AND PIPING SECURED TO BLOCKING, ALL UNNERGROUND TOOL MARKS AND FITTINGS TO BE COVERED WITH PIPE TAPE PRIMER THEN WRAPPED WITH PIPE TAPE TO ACHIEVE A 40 MIL THICKNESS OF PIPE WRAP, THIS IS TO BE LEFT UNCOVERED UNTIL FINAL INSPECTION, CONTRACTOR TO PAY REINSPECTION FEE PRIOR TO FINAL INSPECTION
03/22/2011 PLUMBING - FINAL Cancelled IVRS - RI canceled
1) NO ACCESS AT 3:35 PM. PLEASE SEE NOTES FOR 2432 N. SHADE TREE LN.
03/17/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*