Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11PL00425

Parcel: 133140550

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/01/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/17/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
03/10/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection PROVIDE A RELIEF DRAIN FOR T&P VALVE, INSTALL A SEDIMENT TRAP AT GAS CONNECTION TO WATER HEATER AND FURNACE, SECURE VENT CONNECTORS WITH 3 SCREWS AT JOINTS, INSTALL FLASHINGS AT ROOF PENETRATIONS, SECURE PIPING WITH APPROVED PIPE CLAMPS AND USE WEATHER PROOF SCREWS.