Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11PL00330
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
02/24/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 12 PSI TEST IS NOT HOLDING 2) PROVIDE SEDIMENT TRAPS AT FURNACE AND WATER HEATER 3) REPLACE T & P VALVE AND PIPE DOWNHILL 4) NO FLEX ALLOWED IN T & P DRAIN |