Permit: T11PL00292

Parcel: 122060450


Addresses:

4307 E LESTER ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/10/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/07/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection 1. 3/4' GAS SUPPLY FOR 135,000 BTU AT 110 FEET. IS UNDERSIZED. 2. SUPPORT/SERVICE DROP TO WATERHEATER. 3. CORRECT LEAKING RELIEF VALVE. 4. ACCESS TO FURNACE. 5. PERMIT FOR FURNACE?
03/01/2011 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 1/2' PIPING TO NEW ROOF TOP UNIT IS UNDERSIZED, AND NOT UNDER TEST. NEW FURNESS AND WATER HEATER REQUIRE PERMITS AND INSPECTIONS. WATER HEATER REQUIRES APPROVED VENTING, PROPER T AND P DRAIN, ANEW GAS FLEX AND SEDIMENT TRAP. ACCESS TO NEW FURNESS.
02/23/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection 1) NO ANSWER AT 940-9115 AM
2) NO MESSAGE