Permit: T11PL00162

Parcel: 134261640


Addresses:

6907 E PRINCETON DR

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/01/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/31/2011 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FAILURE TO MAKE ALL NECESSARY CORRECTIONS LISTED ON 1/27/11 INSPECTION WILL RESULT IN FUTURE REINSPECTION FEES. PLEASE READ ITEMS #1 AND 3
2) IT IS IN YOUR BEST INTEREST TO CALL IN PERMIT #T10EL01716 AND HAVE IT FINALED
3) CAP OR REMOVE THE OLD GAS PIPING IN OLD FURNACE/WATER HEATER AREA
01/27/2011 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PIPE TAPE PRIMER, THEN PROVIDE PIPE TAPE TO ACHIEVE A 40 MIL THICKNESS OF WRAP ON ALL UNDERGROUND FITTINGS AND TOOL MARKS
2) COMPLETE THE ENTIRE GAS PIPING SYSTEM WITH TEST INCLUDING BONDING, APPROVED GAS SHUT OFF VALVES, COMBUSTION AIR AND VENTING REQUIREMENTS
3) PROVIDE ACCESS TO ALL GAS PIPING IT IS TO BE PROPERLY SUPPORTED AND SECURED
4) IF YOU HAVE A NEW A/C FURNACE UNIT PROVIDE PROOF OF INSPECTION OR OBTAIN A PERMIT FOR THIS
5) LIST MAY NOT BE COMPLETE