Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2011 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) CORRECT SLOPE ON VENT 2) PROVIDE AN AG OF PRV 3) PROVIDE A DRAIN VALVE |
|
| 01/24/2011 | PLUMBING - FINAL | Cancelled | CANCELLED PER HOMEOWNER #261-2691 | |
| 01/24/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/21/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE A TEST ON SYSTEM USING A 15 PSI GAUGE AND 10 PSI AIR PRESSURE 2) PROVIDE INSTALLATION INSTRUCTIONS FOR TANKLESS WATER HEATER, NEED APPROVED VENTING 3) T & P MAY NOT BE TRAPPED 4) SECURE ALL PIPING, INCLUDING AT STOVE 5) GAS FLEX UNDERSIZED 6) POOL BOILER REQUIRES A RELIEF VALVE 7) PROVIDE ELECTRICAL BONDING OF GAS SYSTEM 8) SEAL SCREW HOLES INTO ROOF |