Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/13/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WATER HEATER TEMPERATURE AND PRESSURE RELIEF TO GRAVITY DRAIN WITH RIDGID PIPING (NO FLEXES) 2) PROVIDE APPROVED VENTING SYSTEM FOR WALL HEATER 3) PROVIDE APPROVED GAS SHUT VALVE FOR WALL HEATER 4) VENT FROM FURNACE TO BE IN CORRECT DIRECTION OF FLOW, EXTENDED UP WITH DBL WALL TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' 5) WATER HEATER VENT TO EXTEND 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' WITH DBL WALL VENT PIPING AND CAP 6) PROVIDE BONDING OF GAS SYSTEM |