Permit: T11PL00055

Parcel: 122030660


Addresses:

2024 N BELL AV #01

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/24/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/21/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) AT WATER HEATER #1, INSTALL ALL VENT PIPE FITTINGS IN THE CORRECT DIRECTION OF FLOW, SEE PIPE ON FITTINGS ( A SHORT SINGLE WALL CONNECTION AT PIPE WATER HEATER CONNECTION WOULD HELP) GLUE ALL CPVC JOINTS. WRAP ALL TOOL MARKS BELOW GRADE. YOU NEED "FLARE" CAPS ON FLARE VALVES THAT WILL NOT BE CONNECTED. REMOVE 1 X 1/2 TEE AT METER
01/20/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
01/19/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
01/13/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
01/12/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) 10 PSI TEST REQUIRED
2) SUPPORT AND SECURE GAS PIPING
3) SUPPORT WATER HEATER ON A SOLID LEVEL BASE
4) SECURE WATER HEATER VENT MINIMUM CLEARANCES
5) COMPLETE PIPING AT WATER HEATER AND DRYER
6) PIPE T & P TO EXTERIOR WITH APPROVED MATERIALS
7) CHECK RELIEF VALVES FOR PROPER OPERATION
8) NEW FLEXES OF PROPER SIZE REQUIRED
9) THIS ENTIRE SYSTEM HAS BEEN REPIPED WITHOUT INSPECTION AND REQUIRES A PLAN AND MANY CORRECTIONS