Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) WATER FLEX IS NOT APPROVED FOR USE ON T & P RELIEF DRAIN. HARD PIPE T (COPPER) 2) SUPPORTS ON ROOF ARE REQUIRED TO BE WEATHER REISTANT (REDWOOD, PRESSURE TREATED OR METAL) |
|
| 01/21/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RETEST BECAUSE OF JACK INSTALLATION 2) PROVIDE MINIMUM CLEARANCE AROUND B VENT 3) SECURE VENT WITH SCREWS 4) TERMINATE RELIEF VALVE 5) INSTALL SEDIMENT TRAP |
|