Permit: T11PL00013

Parcel: 134100370


Addresses:

8002 E SCARLETT ST

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/07/2011 PLUMBING - FINAL Partial Approval 1) SECURE VENT CONNECTORS, PROVIDE REQUIRED CLEARANCES (6" ON SINGLE WALL, 1" ON TYPE B) SUPPORT AND SECURE PIPING AT WATER HEATER
2) OK TO COVER WITH CLEAN FILL ONLY-NO ROCKS
3) VAC BREAKERS REQUIRED ON ALL ?