Permit: T11PL00006

Parcel: 125041370


Addresses:

2133 E 2ND ST

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
01/06/2011 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
01/05/2011 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YARD LINE REQUIRES A MINIMUM 12" COVER
2) PVB IS REQUIRED TO BE 12" ABOVE THE HIGHEST OUTLET
3) 1 P MAKE THREADS MAY NOT BE USED WITH PVC FEMALE THREADS
4) REAM ALL COPPER JOINTS AND REMOVE EXCESS FLUX
5) OK TO INSTALL METER BOX