Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2011 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 01/05/2011 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YARD LINE REQUIRES A MINIMUM 12" COVER 2) PVB IS REQUIRED TO BE 12" ABOVE THE HIGHEST OUTLET 3) 1 P MAKE THREADS MAY NOT BE USED WITH PVC FEMALE THREADS 4) REAM ALL COPPER JOINTS AND REMOVE EXCESS FLUX 5) OK TO INSTALL METER BOX |